NSX通讯遥控断路器的分合闸报文分别是多少?
问题描述:
NSX通讯遥控断路器的分合闸报文分别是多少?所属产品线:
Compact NSX解决方法:
举例:实验设置,断路器的通讯模块地址:2
波特率:19200,奇偶校验:Even
完整的Modbus分闸指令为:
02 10 1F 3F 00 14 28 03 88 00 0A 11 01 00 01 30 30 30 30 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 1F 53 1F 54 3E EF
合闸指令为:
02 10 1F 3F 00 14 28 03 89 00 0A 11 01 00 01 30 30 30 30 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 1F 53 1F 54 FC AE
是否有帮助?